    EJA110A-DMS5A-22ND Yokogawa EJA110A Differential Pressure Transmitter

    Ask Lasest Price
    Brand Name : Yokogawa
    Model Number : EJA110A-DMS5A-22ND
    Certification : CE
    Delivery Time : 6-8weeks
    • Product Details
    • Company Profile

    EJA110A-DMS5A-22ND Yokogawa EJA110A Differential Pressure Transmitter

    EJA110A-DMS5A-22ND Yokogawa EJA110A Differential Pressure Transmitter


    Ordering Information
    Model: EJA110A - Differential pressure transmitter
    Output Signal: -D - 4 to 20 mA DC with digital communication (BRAIN protocol)
    Measurement span (capsule): M - 1 to 100 kPa {100 to 10000 mmH2O} {4 to 400 inH2O} {10 to 1000 mbar}
    Wetted parts material?: S# - [Body]2 SCS14A; SUS316L3; [Vent plug] SUS3164
    Process connections: *5 - without process connector (1/4 NPT female on the cover flanges)
    Bolts and nuts material: *A - SCM435: [Maximum working pressure] 16 MPa {160 kgf/cm2}5
    Installation: -2 - Vertical impulse piping type, right side high pressure, process connector upside6
    Electrical connection: *2 - 1/2 NPT female, two electrical connections without blind plug
    Integral indicator: *N - (None)
    Mounting bracket: D - SUS304: 2-inch pipe mounting (L type)
    NOTE:
    The '*' marks indicate the most typical selection for each specification.
    The '#' marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of SUS316 material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
    1. Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user's process fluids. Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam. Contact Yokogawa for detailed information of the wetted parts material.
    2. Indicates material of cover flanges and process connectors.
    3. Diaphragm material is Hastelloy C-276 or ASTM N10276. Other capsule wetted parts materials are SUSF316L, SUS316L or ASTM grade 316L.
    4. SUS316 or ASTM grade 316.
    5. For Capsule code L when combined with Wetted parts material code H, M, T, A, D, and B, the maximum working pressure is 3.5 MPa {35 kgf/cm2}.
    6. If necessary, specify Mounting bracket code C, D or K.

    The EJA-A series is Yokogawa's most successful pressure transmitter line. First released in 1991, it continues to offer high


    performance and high reliability for any application. With an installed base of over 4-1/2 million EJA-A transmitters worldwide, it


    has a proven track record that makes it a true industry workhorse.


    The EJA110A is the Traditional-mount Differential Pressure Transmitters in the series.


    EJA110A features include:

    • 0.065% Accuracy
    • 0.1% Stability per 5 years
    • 2,300 psi MWP

    Model Number: EJA110A

    • Output: 4-20mA with HART protocol

    • Accuracy: ±0.065% of span

    • Cover Flange: SUS316, Hastelloy C-276, Monel

    • Power Supply: 10.5 to 42V


    • EJA110A Overview

    Measurement Types
    Primary VariableDifferential Pressure (DP)
    Reference Accuracy
    Primary Variable±0.065% of DP Span
    Long Term Stability (All Normal Operating Conditions)
    Primary VariableM, H, or V Capsule: ±0.1% of URL per 5 years
    L Capsule: ±0.1% of URL for 1 year
    Maximum Pressure Limit (MWP)
    All Capsules2,300 psi
    Over-pressure Effect
    Primary Variable±0.03% of URL
    Rangeability
    Primary VariableM, H, or V Capsule: 100:1
    L Capsule: 20:1
    Burst Pressure (Absolute)
    All Capsules10,000 osi


    Our advantage Products:
    【Honeywell】Module DCS / PLC
    【Emerson】DeltaV Module / Servo Motor
    【ABB】Input Output Module
    【AB】Module / Touch Screen
    【Rosemount】Pressure and Temperature Transmitter
    【Yokogawa】Pressure Transmitter
    【Yaskawa】Servo Drive / Servo Motor
    【Mitsubishi】Servo Drive / Servo Motor
    【GE】IC69 Series PLC/ Fanuc Servo Motor and Drive
    (Modicon,SMC,SICK,NORGREN,Siemens etc.)




    Quality EJA110A-DMS5A-22ND Yokogawa EJA110A Differential Pressure Transmitter for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Wisdomlong Technology CO.,LTD
    *Subject:
    *Message:
    Characters Remaining: (0/3000)