Sign In | Join Free | My himfr.com
Home > Digital I O Module >

1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS

    Buy cheap 1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS from wholesalers
     
    Buy cheap 1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS from wholesalers
    • Buy cheap 1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS from wholesalers
    • Buy cheap 1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS from wholesalers

    1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS

    Ask Lasest Price
    Brand Name : GE
    Model Number : 1756-ENBT
    Price : negitiation
    Payment Terms : T/T, Western Union
    Supply Ability : 100
    Delivery Time : 3-5days
    • Product Details
    • Company Profile

    1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS

    1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS



    Specifications for ControlLogix EtherNet/IP Bridge 1756-ENBT
    ETHERNET/IP COMMUNICATION BRIDGE MODULE
    CONTROLLOGIX
    10/100 MBPS
    24 VDC
    3 MA
    128 LOGIX CONNECTIONS
    REPLACED BY 1756-EN2T


    OTHER SUPERIOR PRODUCTS

    Yasakawa Motor, Driver SG-Mitsubishi Motor HC-,HA-
    Westinghouse Modules 1C-,5X-Emerson VE-,KJ-
    Honeywell TC-,TK-GE Modules IC -
    ABB ModuleAB Module 1756-,1759- Tourch Screen 2711-
    Mitsubishi Drive MR- , Motor HA -,HCEmerson MoudlesVE- ,KJ -
    Fanuc motor A0-, DriveYokogawa transmitter EJA-
    Rosemount Transmitter 3051-Schneider Module 140-
    Panasonic Motor , Drive MH-Siemens Module 6ES-, Touch Screen 6AV-

    EtherNet/IP Network Configuration
    EtherNet/IP Communication Modules
    1756-ENBT, 1756-EN2F, 1756-EN2T, 1756-EN2TP, 1756-EN2TPK, 1756-EN2TPXT, 1756-EN2TR, 1756-EN2TRXT,
    1756-EN2TSC, 1756-EN2TXT, 1756-EN3TR, 1756-EWEB, 1768-ENBT
    CompactLogix 5370 Controllers
    EtherNet/IP Adapters
    1734-AENT, 1734-AENTR, 1769-AENTR, 1794-AENT, 20-COMM-E, 22-COMM-E, 20-750-ENETR
    Embedded Switches
    1783-ETAP, 1783-ETAP1F, 1783-ETAP2


    A backplane communication error may occur and trigger a complex sequence of events which can result in a 1756-L6X or 1756-L55 controller experiencing a major nonrecoverable fault, or cause other communications modules to assert. This anomaly can be triggered by using a 1756-ENBT module with unconnected message traffic in a system that does not include one or more of the following modules in the same chassis with the 1756-ENBT module: • 1756-EN2F • 1756-EN2T • 1756-EN2TR • 1756-EN3TR • 1756- EN2TXT • 1756-CN2/B • 1756-CN2R/B • 1756-CN2RXT • 1756-DNB/C • 1756-DNB/D • 1756-L7X • 1756-RM


    As new firmware revisions of the 1756-ENBT module are released, previous versions of RSLogix 5000 software may not have those
    newer 1756-ENBT module firmware revisions available in the Logix 5000 device selection list. To use a newer firmware revision of the
    1756-ENBT module with an older version of the RSLogix 5000 software, add an older 1756-ENBT firmware revision to the project
    and select compatible keying as the keying option. For example, if using version 16.00.00 of RSLogix 5000 software, selecting a 4.005
    firmware revision with compatible keying will allow a revision 6.006 1756-ENBT module to function.


    For I/O control, use RSLogix 5000 software version 8.02.00 or later. However, the 1756-ENBT module works with the 1756-ENET/B
    selection in version 7.00.00 if the Compatible keying option is used.
    – For Gateway applications, there are no software compatibility issues
    with RSLogix 5000 software.
    • RSLinxClassic software, version 2.30.01 or later


    Quality 1756-ENBT ControlLogix EtherNet/IP Bridge Module 128 LOGIX CONNECTIONS for sale